Lamborghini Caloreclima 310 PM/2-E Manual Para La Instalación Y El Mantenimiento página 40

Ocultar thumbs Ver también para 310 PM/2-E:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

GAS REGULATION
The maximum flow and start up flow must be regulated.
Ensure that there are no leaks from the gas ramp.
MAXIMUM FLOW
Install a pressure gauge to measure the gas pressure at the burner head;
Set the gas valve to its maximum opening;
With the burner operating, regulate the stabilizer (if present) until the desired flow has been achieved (read
on the meter); check the pressure indicated on the pressure gauge;
Regulate the valve by closing it until the pressure indicated on the pressure gauge starts to decrease.
this point the desired maximum flow has been set and checked by both the stabilizer and the gas valve.
stabilizer
CHECK OF THE GAS QUANTITY ON START-UP
The check of the gas quantity on start-up is performed by using the following formula:
Ts x Qs ≤ 100
where
Ts
= Safety interval in seconds
Qs = Energy released in the safety interval expressed in kW
The Qs value is obtained by :
where
Q1 is the flow rate in litres released in 10 starts within the safety interval.
Ts1 is the sum of the actual safety interval in 10 starts.
Qn is the nominal power.
safety valve
main valve
pressure gauge
0
A t
Tabla de contenido
loading

Este manual también es adecuado para:

430 pm/2-e

Tabla de contenido