Error Codes - EAS ELECTRIC ETH220VMA Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

OPERATION PARAMETER
FAN SPEED
600R/MIN
IDU TARGET FREQUENCY
FREQUENCY LIMITED TYPE
SUPPLY VOLTAGE
DC GENERATRIX VOLTAGE
DC GENERATRIX CURRENT
ADDRESS
The power consumption parameter is preparatory. some parameter is not be activated in the system, the parameter will
show "--"
The heat pump capacity is for reference only, not used to judge the ability of the unit. The accuracy of sensor is ±1℃.
The flow rates parameters are calculated according to the pump running parameters,the deviation is different at different flow
rates,the maximum of deviation is 25%.

13.4 Error codes

When a safety device is activated, an error code will be displayed on the user interface.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
In case this procedure for resetting the safety is not successful, contact your local dealer.
ERROR
MALFUNCTION
CODE
OR PROTECTION
Water flow fault (E8
displayed 3 times)
Phase loss or neutral wire and
live wire are connected
reversely
Communication fault between
controller and main control
board of hydraulic module
Final outlet water temp. sensor
(T1) fault.
Water tank temp. sensor
(T5) fault.
#01
OPERATION PARAMETER
TW_O PLATE W-OUTLET TEMP. 35°C
46Hz
TW_I PLATE W-INLET TEMP.
5
T2 PLATE F-OUT TEMP.
230V
T2B PLATE F-IN TEMP.
420V
Th COMP. SUCTION TEMP.
18A
Th COMP. DISCHARGE TEMP.
ADDRESS
7/9
NOTE
1.The wire circuit is short connected or open. Reconnect the wire
correctly.
2.Water flow rate is too low.
3. Water flow switch is failed, switch is open or close continuously,
change the water flow switch.
1.Check the power supply cables should be connected stable, to avoid
phase loss.
2.Check the power supply cables sequence, change any two cables
sequence of the three power supply cables.
1.The wire doesn't connect between wired controller and unit. connect
the wire.
2.Communication wire sequence is not right. Reconnect the wire in
the right sequence.
3. Whether there is a high magnetic field or high power interfere, such
as lifts, large power transformers, etc..
4. To add a barrier to protect the unit or to move the unit to the other
place.
1. Check the resistance of the sensor
2. The T1 sensor connector is loosen. Reconnect it.
3.The T1 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive.
4.The T1 sensor failure, change a new sensor.
1. Check the resistance of the sensor
2.The T5 sensor connector is loosen. Reconnect it.
3.The T5 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4.The T5 sensor failure, change a new sensor
61
#01
OPERATION PARAMETER
T3 OUTDOOR EXCHARGE TEMP. 5°C
T4 OUTDOOR AIR TEMP.
30°C
TF MODULE TEMP.
35°C
P1 COMP. PRESSURE
35°C
ODU SOFTWARE
5°C
75°C
HMI SOFTWARE
ADDRESS
8/9
FAILURE CAUSE
AND CORRECTIVE ACTION
'
#01
5°C
55°C
2300kPa
01-09-2018V01
01-09-2018V01
9/9