TABLE 3: Copper Cable Length in Feet (Service to Motor)
G-Series Motors: 1 Ph, 2-Wire Cable, 60 Hz. Wire Size
HP
Volt
14
0.5
115
110
0.5
230
438
0.75
230
365
1
230
304
G-Series Motors: 1 Ph, 3-Wire Cable, 60 Hz. Wire Size
HP
Volt
14
0.5
230
348
.75
230
267
1
230
203
NOTE:
1.
Maximum wire lengths shown maintain motor voltage at 95% of
service entrance voltage, running at maximum nameplate amperes.
If service entrance voltage will be at least motor nameplate voltage
under normal load conditions, 50% additional length is permissable
for all sizes.
2. Sizes given are for copper wire. For aluminum wire go two sizes
larger (i.e., if table lists #12 (3mm
aluminum wire.)
INSTALLATION WIRING INSTRUCTIONS
Single Phase, 3 Wire
Hazardous voltage. Can shock, burn, or kill.
Ground control box, all metal plumbing, and motor frame
with copper wire in compliance with Canadian Electrical Code or National
Electrical Code and local codes. Use ground wire at least as large as the
wires supplying power to motor.
At well head, connect ground wire to grounding terminal that meets
Canadian Electrical Code or National Electrical Code requirements that
apply. For more information, contact local code officials.
Permanently close all unused openings in this and other equipment.
Disconnect power before working on or around control box, pipes, cable,
pump, or motor.
NOTICE: Install control box vertically on wall with top side up.
3-Wire pumps have three power supply wires (Red/Black/Yellow) and one
ground wire (Green).
Attempting to operate 3 wire pump without a control box will burn out the
motor.
Installations must include circuit and component protection in
compliance with U.S. National Electrical Code or Canadian Electrical
Code, Part 1.
If main overload trips, look for:
1. Shorted Capacitor
2. Voltage Problems
3. Overload or locked pump.
NOTICE: Use only control box specified for your 3-wire pump. Make sure
motor and control box match (Table 4). FAILURE TO DO SO WILL VOID
WARRANTY.
Table 4: Control Box Chart
HP
Voltage
1/2
230
3/4
230
1
230
12
10
8
6
174
278
440
685
697
1112
1761
2740
581
927
1468
2284
484
772
1223
1903
12
10
8
6
553
883
1398
2175
425
678
1074
1671
323
515
815
1269
) copper wire, use #10 (5mm
2
Control Box No.
123329
123330
123331
Wire Size, AWG
4
3
2
1092
1373
1734
4369
5492
6936
3641
4577
5780
3034
3814
4817
Wire Size, AWG
4
3
2
3467
4359
5505
6935
2664
3349
4229
5328
2023
2543
3211
4045
Fig. 1A – 3 wire - 1/2 thru 1 HP quick disconnect box.
Follow color coding when connecting control box.
(Yellow to Y, Red to R, Black to B)
)
2
Single Phase, 2 Wire
2-Wire pumps have two power supply wires (Black) and one ground
wire (Green). DO NOT USE a control box with a 2-wire motor.
See Figure 1B for correct hook-up information for 115 or 230 Volt
2-Wire motors only.
Fig. 1B – Single phase, 2 Wire Connections
3
1
0
00
2184
2757
3479
8738
11029
7281
9191
11596
6068
7659
9663
1
0
00
8753
6725
8485
5106
6442