FLOW SWITCH INSTALLATION – SCMAX
FLOW SWITCH INSTALLATION – SCMAX
Locate a suitable position to install the flow switch. The flow switch should be installed on a straight section of pipe
Instalação do interruptor de caudal
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, valves, or fittings.
Locate a suitable position to install the flow switch. The flow switch should be installed on a straigh
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable response.
Localize a posição adequada para instalar o interruptor de caudal. O interruptor de caudal deve ser instalado
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, v
numa secção reta do tubo com um mínimo de diâmetros de 5 tubos, em qualquer uma das direções entre
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable res
o interruptor de caudal e as bombas, válvulas ou conexões. Isto assegura que a patilha fica exposta a u
caudal não turbulento, dando uma resposta constante e estável.
5 x pipe dia.
minimum.
O interruptor da caudal pode ser instalado em tubos verticais ou horizontais, na parte lateral ou superior do tubo.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of the pipe.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of th
The flow switch should not be mounted on the underside of horizontal pipes.
O interruptor de caudal não deve ser montado na parte inferior dos tubos horizontais.
The flow switch should not be mounted on the underside of horizontal pipes.
Logo que seja selecionado um local, efetue um furo de 32 mm no tubo.
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
The flow switch can be installed in vertical or horizontal pipes, either on the side or o
The flow switch should not be mounted on the underside of horizontal pipes.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
58