Parameter menu

PARAMETER
PARAMETER
Motor type selection
Standard motor (4-pole) - (and all existing codes with the exception of the following codes for the value
)
Slow motor (6-pole) - (R20/302, R20/502, R21/368, H23/282, R41/832, R41/833)
Automatic closure after pause time (from gate completely open)
Disabled.
From 1 to 15 of gate closure attempts after photocell is triggered.
Once the number of attempts set is reached, the gate remains open.
Automatic gate closing after mains power outage
Disabled. The gate does not close automatically when mains power is restored.
Enabled. If the gate is NOT completely open, when mains power is restored, the gate closes after a 5
The gate closes in "position recovery" mode (see chapter 17).
Selecting step mode control function (PP)
Open-stop-close-stop-open-stop-close...
The automatic closing timer restarts if a new step mode command is received.
Step mode commands are ignored while the gate is opening. This allows the gate to open completely and
prevents the gate from closing when not required.
If automatic closing is disabled (
manoeuvre
The automatic closing timer does NOT restart if a new step mode command is received.
Step mode commands are ignored while the gate is opening. This allows the gate to open completely and
prevents the gate from closing when not required.
If automatic closing is disabled (
manoeuvre
Open-close-open-close.
Open-close-stop-open.
Flashing warning signal for 1 to 10 seconds prior to every manoeuvre.
Condominium function for partial open command (PED)
Enabled. Partial commands are ignored during gate opening.
64
VALUE
.
.
), the condominium function automatically attempts a closing