NOTICE!
For all Bosch fire panels, the alarm contact resistance has to be
changed to 680 Ω.
Installation
See Figure 1, Page 3.
Install the LSN base only together with the FAA-500-BB Ceiling Mount Back
Box or with FAA-500-SB-H Surface Mount Back Box. Ensure an even
arrangement of boxes and bases for a harmonious optical impression.
1.
Installation with a FAA-500-BB Ceiling Mount Back Box: Place the base
in the ceiling mount back box so that the triangular mark (4) on the
outer rim of the back box matches with the single guideway (5).
Installation with a FAA-500-SB-H Surface Mount Back Box: Ensure the
correct alignment of the base.
2.
Turn the base until the fastening screws are in the middle of the long
slit (3).
3.
Slightly turn each base until the bases align in one direction.
4.
Tighten the four screws.

Technical Data

Wire gauge
Hosing material and color
Dimensions (Ø x H)
Weight (without/with packaging) 200 g/280 g
F.01U.002.683 | 4.0 | 2011.09
2
0,3 mm
- 3,3 mm
Polycarbonate, signal white (RAL 9003)
145,6 mm x 63,5 mm
FCA-500-EU | FCA-500-E-EU
2
(22 AWG - 12 AWG)
Bosch Sicherheitssysteme GmbH