Typical Type 3R, NH Series Ventilated Enclosure Assembly for Three Phase and Single
Phase Transformers.
Notes:
1.
Handling - units are designed to be raised by a fork lift from underneath the pallet. Final positioning of the unit
with the pallet removed can be via a fork lift under the transformer with the forks between the channels.
2.
Shipping - units are shipped on pallets which are to be removed at installation.
3.
Installation - This transformer can be installed indoor or outdoor providing a degree of protection against falling
rain, sleet and external ice formation.
4.
All general purpose/drive isolation transformers should be located away from walls or any other obstructions at
least 6 inches when floor mounted and 4 inches when wall mounted.
5.
DO NOT block bottom ventilation area.
Removable front
access panel
Position fork
lift under pallet
FIGURE 1
For final positioning
with pallet removed,
fork lift points are under
the transformer
- 9 -
Cable entrance
knockouts (2 per side)