Introduction to Quick Setup
This Quick Setup will guide you through EMC correct
installation of the frequency converter by connecting
power, motor and control wiring (fig. 1). Start/stop
of motor is to be done with the switch.
For VLT 5122 - 5500 380 - 500 V, VLT 5032 - 5052
200 - 240 V AC and VLT 5075 - 5250 525 - 600 V,
please refer to Technical data and Installation regarding
mechanical and electrical installation.
1. Mechanical Installation
VLT 5000 frequency converters allow side-by-side mounting. The necessary cooling demands a free air
passage of 100 mm above and below the frequency converter (5016-5062 380-500 V, 5008-5027 200-240
V and 5016-5062 550-600 V must have 200 mm, 5072-5102, 380-500 V 225 mm).
Drill all holes by using the measurements stated in the table. Please note the difference in unit voltage. Place
the frequency converter on the wall. Tighten up all four screws.
All the below listed measurements are in mm
VLT type
Bookstyle IP 20, 200–240 V, (Fig. 2)
5001 - 5003
5004 - 5006
Bookstyle IP 20, 380–500 V (Fig. 2)
5001 - 5005
5006 - 5011
Compact IP 54, 200–240 V (Fig. 3)
5001 - 5003
5004 - 5006
5008 - 5011
5016 - 5027
Compact IP 54, 380–500 V (Fig. 3)
5001 - 5005
5006 - 5011
5016 - 5027
5032 - 5062
5072 - 5102
Compact IP 20, 200–240 V (Fig. 4)
5001 - 5003
5004 - 5006
5008
5011 - 5016
5022 - 5027
Compact IP 20, 380–500 V (Fig. 4)
5001 - 5005
5006 - 5011
5016 - 5022
5027 - 5032
5042 - 5062
5072 - 5102
MG.50.A2.62 - VLT is a registered Danfoss trademark
A
B
C
a
b
395
90
260
384
70
395
130 260
384
70
395
90
260
384
70
395
130 260
384
70
460
282 195
260
258
530
282 195
330
258
810
350 280
560
326
940
400 280
690
375
460
282 195
260
258
530
282 195
330
258
810
350 280
560
326
940
400 280
690
375
940
400 360
690
375
395
220 160
384
200
395
220 200
384
200
560
242 260
540
200
700
242 260
680
200
800
308 296
780
270
395
220 160
384
200
395
220 200
384
200
560
242 260
540
200
700
242 260
680
200
800
308 296
780
270
800
370 335
780
330
VLT® 5000 Quick Setup
Fig. 1
Fig. 2
Fig. 3
Fig. 4
9