G
B
SAFETY STRIP SELF-TEST ALARM (DIP 9 ON)
At the end of the opening if the safety strip monitoring operation is
negative, an alarm indicated by a blinker that lights up twice in a row
before going off for 2 seconds, and by the buzzer (if connected) enabled
for 5 minutes, get into action. In this case the gate cannot open and
normal functions are reinstated only upon repair of the safety edge and
by pressing one of the enabled switches.
STOP BUTTON (COM - STOP)
During any operation, the STOP button blocks the bar.
If pressed with the bar fully open automatic closure is excluded
temporarily (if selected through DIP3 ON).
Therefore a new command operation is required to close it.
On the following cycle the «automatic closure" operation is enabled
again (if selected through DIP3 ON).
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES
ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds,
or if photocell fails or remain engaded for more than 60 seconds, the
OPEN 1, OPEN 2, CLOSE, and K BUTTON commands will work only
in dead man mode.
The signal that this mode has been activated is given by the blinking of
the programming led.
With the blinking of the programming led, the opening and closing
operation are allowed only with the command button pressed and held.
The radio commands and that of automatic closing, will be excluded,
since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired,
second, all standard commands that were selected, such as step by
step, automatic mode, radio commands and automatic closing start
functioning again.
Note 1: during this functioning in dead man mode, in case of damage to
the safety strips (or photocells) the photocells (or safety strips)
still work by interrupting the operation in progress.
Note 2: the stop command is not to be considered a safety command
that can be bypassed in this mode. Therefore, when pressed or
damaged, it will not allow any movement of the gate.
The dead-man operation is only an emergency operation which
must be activated for a very short period and with the complete
installation at sight so to have a secure and safe control of the
system. As soon as possible however, the failing safety devices
must be repaired and activated.
BLINKER 230V 40W
You can control the blinker output, through DIP 13:
DIP 13 ON => RAPID S, RAPID N and RAPID PARK types of barrier
come with the blinker already connected.
The blinker is power supplied at intermittence, with 500 mS on/off blinks
during opening and 250 mS on/off blinks during closure.
In case of safety-edge alarm or safety-edge auto-test the blinker output
changes intermittence turning to 2 short blinks before going off for 2
seconds.
BUZZER (Optional) (COM-BUZZER)
During opening the buzzer shall emit an intermittent acoustic signal
shortening acoustic signal intervals during closure. When the safety
devices (alarm) get into action, this acoustic signal increases the
intermittence frequency. Power supplied to buzzer 200 mA at 12Vdc.
GATE OPEN WARNING LIGHT (COM-SIGNAL)
Its function is to signal when the barrier is open, partially open or not
totally closed. It turns off only when the gate is totally closed. The
buzzer goes off only with the barrier totally closed.
N.B.: If push button panels or lamps are overused, the logic system of
the control board will be jeopardised possibly leading to the block
of operations.
DIP 12 - CONTROLLING SLOW-DOWN
OFF - Operation control with low speed limit switches connected
separately (see photo A) - LIMIT SWITCHES FIXED ON THE
BALANCE SPRING BARS (for PARK control panel)
ON - Operation control with low speed limit switches connected in
T
- Humidity
- Power supply voltage
- Frequency
- Maximum card absorbtion
in automatic after 1
- Network microswitch
- Barrier open warning light maximum power
- Maximum power at blinker output
- Voltage available for photocells and accessories 500mA 12Vdc
- Voltage available on the radio connector
R
- Reception frequency
- Impedance
- Sensitivity
- Excitation time
- De-excitation time
- Codes in store
- All the inputs must be used as clean contacts given that the power
- Any external circuits connected to the outputs of the control board,
- All the inputs are run by a programmed integrated circuit which carries
32
32
parallel (see photo B) - LIMIT SWITCHES FIXED ON THE
DRIVING SHAFT (the low speed wire can be connected to
LSSC or LSSO)
A
ECHNICAL FEATURES
ADIO TECHNICAL FEATURES (ONLY FOR CRX)
supply is generated internally (safe voltage) in the card and it is set
in a way to guarantee the use of the double insulation and reinforced
compared to parts with hazardous voltage.
must be carried out to make sure the double or reinforced insulation
is used compared to parts with hazardous voltage.
out an auto-test at every start-up operation.
B
< 95% without
condensation
230 or 120V~ ±10%
50/60 Hz
30mA
100ms
3 W (equivalent to
1 lamp of 3W or 5
leds with 2.2 kΩ
resistance in series)
40W with resistive
charge
200mA 12Vdc
433.92MHz
52 Ω
>2.24µV
300ms
300ms
N° 60