Output module CPX−2AA−U−I
(continuation)
Operating voltage supply
Rated voltage
Max. current consumption
at 24 V
Load voltage supply (actuator
supply)
Rated voltage
Undervoltage V
voltage outside of func
tional range)
Load capacity (max. cur
rent consumption at 24 V)
Fuse
Behaviour after end of
overload
Reverse polarity protection
24 V actuator supply
Inverse voltage resistance
Electrical isolation
Between channel and
24 V
OUT
Between the channels
Festo CPX−AX 0811c English
Voltage outputs
V
EL/SEN
DC 24 V ± 25%
Type 100 mA (maximum current
consumption at outputs)
V
OUT
output, same supply potential at all
outputs
DC 24 V ± 25%
(load
17 to 14 V
OUT
(initiates diagnostic message
Undervoltage V
> 4 A (max. permanent current per
module)
Electronic, thermal (operating cur
rent: 4 to 10 A)
Can be parametrised
(s. description P.BE−CPX−AX...)
Yes
Max. 30 V permanent (destruction
limit)
Yes (release electrical isolation by
using the internal actuator supply)
No
Current outputs
(electronics/sensors)
(outputs), one connection per
)
OUT
29