6 – Internal Battery Connection
1
6-2 Internal Battery Connection Procedure
•
Slide a battery string with a red cable into an empty slot within
6
2
the battery compartment. Make sure the battery string is oriented
as shown in the diagram. Note: Start with the empty slots at the
bottom of the battery compartment and work toward the empty
slots at the top of the battery compartment.
3
4
•
7
Slide a battery string with a black cable into an empty slot within
the battery compartment, next to the battery string that you inserted
5
in step 6. Make sure the battery string is oriented as shown in the
diagram. Repeat steps 6 and 7 as needed until all the battery strings
have been inserted into the empty battery slots. Note: Depending
on the model of the UPS system, some battery compartment slots
may remain empty.
6
7
•
Reconnect the fuse block bracket. (The letters on the fuse block
8
bracket should be upright when it is in the correct orientation.)
8
9
•
Connect the blue and white jumper cables on each internal battery
9
10
pack to the corresponding fuse block. The labeling next to the fuse
block identifies the correct fuse block for each cable.
11
12
•
10
Insert the battery cartridge fuses into each fuse block. The fuses are
interchangeable. Make sure the fuses are firmly snapped into place.
Warning: Battery cartridge fuses must be inserted last due to
potential arcing of connectors. Blown fuses must be replaced
by a qualified electrician. Replace only with fuses of the same
13
type and rating.
14