Troubleshooting
This section describes possible system problems and their solutions:
Always perform the following preliminary checks before referring to the troubleshooting table:
Perform a complete visual inspection of the LuNAR, for signs of mechanical damage, loose
connections or torn wires.
Check the connections of the incoming AC power source.
Trouble
ProSYS Configuration of
detectors fails/not accepted by
the system
Tamper indication while working
in the BUS mode
Tamper indication in the Relay
or BUS mode
Walk test cannot be initiated via
the ProSYS keypad
Green LED doesn't operate
during Walk test - MW channel
does not function
Meaning
ID configuration
problem
Tamper
connection
malfunction
Tamper probably
not closed
Wrong code
Industrial LuNAR
is configured (via
the ProSYS) to
the "MW disable
on DISARM"
during ProSYS's
DISARM mode
Industrial LuNAR
operating in
Bypass mode
due to "Bypass
MW channel
mode"
Industrial LuNAR DT AM Grade 3 Installation Guide
Response
Disconnect all power sources,
configure the desired IDs and
reconnect power again
Verify that both DIP 8 and 9 are in
ON position
Visually verify that ceiling tamper
and spring are correctly installed
Insert the appropriate code
Normal behavior
Reset the detector.
If MW channel trouble reoccurs,
replace the detector with a new one
21