Risco Industrial LuNAR DT AM Grade 3 Guia De Instalacion página 19

Detector para montaje en techos altos
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Relay Mode Configuration (DIP
switch 6=OFF)
:
DIP switch
Description
Number
1
Used to determine the operation of the ACT
DIP switch ON: ACT is enabled
DIP switch OFF: ACT is disabled (default factory)
2
Used to determine the operation of the detector's LEDs
Dip switch ON: LEDs are enabled (default factory)
DIP switch OFF: LEDs are disabled
3
Used to determine the operation of the "Green Line" (See Note below)
DIP switch ON: "Green Line" is enabled
DIP switch OFF: "Green Line" is disabled (default factory)
4
Used to determine the type of Self Test (See Note below)
DIP switch ON: Local Self Test:
In case the local self test fails, the FAULT/AM Relay is activated for a period of 2.5 secs.
DIP switch OFF: Remote Self Test (default factory):
In case the remote self test passes, the Alarm Relays are activated for a period of 5 secs.
In case the test fails, FAULT/AM Relay is activated for a period of 2.5 seconds.
5
Used to determine whether Active IR Anti-Masking is active. (See Note below)
DIP switch ON: Enable
DIP switch OFF: Disable (default factory)
IMPORTANT:
If the AM is enabled via DIP Switch 5, the cover must be fitted within 1 minute from applying the
power. If the detector is already powered up and DIP Switch 5 is turned on, the unit must be
down powered to reset the AM calibration.
6
Used to determine the detector's connection mode
DIP switch OFF: Relay mode
Used to determine if the Remote Control communication is enabled or disabled.
DIP switch ON: RC communication is always enabled.
DIP switch OFF:
7
"RC"
(default factory)
When an activation signal is applied to the RC input of the terminal block, RC is enabled.
IMPORTANT:
Turn dipswitch 7 "OFF" after installation and when leaving the site for security reasons. This
will prevent unauthorized use of a remote control unit that may be used to disable the detector.
8-9
DIP switches OFF
NOTE:
See Set Terminal Blocks for activation details.
communication
RC
Industrial LuNAR DT AM Grade 3 Installation Guide
depends on the voltage applied to the terminal block
17
Tabla de contenido
loading

Productos relacionados para Risco Industrial LuNAR DT AM Grade 3

Tabla de contenido