INSTALLATION
Step 1. Remove cover and mount unit securely in place.
NOTE:
Keyhole slots not intended as sole means of securement.
Step 2. When connecting unit directly to an electrical box, insert bushing supplied with unit in 7/8 KO.
Step 3. Extend unswitched 24 hour supply of rated voltage and connect per diagram. Cap unused line lead. Connect ground in accordance with NEC or
local codes. Circuit should not be energized at this time.
Step 4. If remote lamps are to be connected, extend DC circuit per Article 700 and 720 of NEC and connect to YELLOW and VIOLET lead provided.
Step 5. Install battery(s) and connect battery RED (+) and BLUE (-) battery leads. Lamps will not light at this time.
Step 6. Turn on AC supply and operate test switch. DC lamps will come on Charge indicator will stay on. Release test switch. DC lamps will extinguish.
Step 7. Replace cover.
MAINTENANCE:
Replace batteries every 12 to 15 years depending ambient temperature. Equipment should be tested regularly in accordance with local
codes.
NOTE: Servicing of any parts should be performed by qualified personnel. For replacement lamps, battery or pc board, see
fixture labels.
OPERATION:
1. To test, depress test switch.* DC lamps will come on. Charge Indicator will stay on.
2. Release test switch. DC lamps will extinguish.
CAUTION: The XR/AA Series Emergency Light is furnished with a sophisticated low voltage battery dropout circuit to protect the
battery from over discharge after the useful output has been reached.
(Allow 24 hours recharge time after installation or power failure for full load testing.)
* For units with the self-diagnostics option, DO NOT TEST until the battery is fully charged (24 hrs). After the unit is fully charged, the
visual indicator will have a steady light (not blinking).
TROUBLE SHOOTING HINTS:
E E M M E E R R G G E E N N C C Y Y L L A A M M P P S S D D O O N N O O T T C C O O M M E E O O N N - - P P I I L L O O T T L L I I G G H H T T O O U U T T B B E E F F O O R R E E T T E E S S T T . .
1. Check AC supply - Be sure unit has 24 hour AC supply.
P P I I L L O O T T L L I I G G H H T T O O N N - - L L A A M M P P S S D D O O N N O O T T L L I I G G H H T T . .
1. Either output shorted or battery not connected.
E E M M E E R R G G E E N N C C Y Y L L A A M M P P S S C C O O M M E E O O N N D D I I M M . .
1. Battery discharged - Permit unit to charge for 24 hours and then re-test. If lamps are still dim, check the charger for charge
function. If functioning properly, replace the battery.