Neighboring mode:  
 
This  mode  is  used  for  Emergency  functions,  and  it  permits  to  broadcast  ALERT  and  EVAC 
messages  sequentially  to  different  zones.  EVAC  message  will  be  broadcasted  by  the  zone 
corresponding  to  input  contact  (Ex:  contact  3  makes  evac  message  to  be  broadcasted  by 
zone 3) and ALERT message will be broadcasted by previous and next zones according to ‐
(0~4) and +(0~4) numbers. (Ex: ‐(0~4) set to 2 and +(0~4) set to 1, contact input 3 activates 
EVAC message to zone 3 and ALERT message to zone 1, 2 and 4.). In this mode you can also 
select  the  play  method,  you  can  select  message  repetitions  with  Specifies  the  number  of 
playback and Number of playback (1~100) or the time with Specifies the time to play and 
Play time (5‐300s). 
5.3.7. Group configuration 
This menu is used to create zone groups.  
There are 120 groups available which can be configured with different zones of the system. These 
groups are only used to operate the system from the Software State and Control menu. 
5.3.8. Import 
This menu is used to Import system configuration. 
The file to import must be exported from the software or extracted from the memory card. It is a 
*.cfg  file.  Press 
, select the file location and press Open, the file will be automatically loaded in 
the system. 
 
Note: only configuration file is imported, audio messages are not included. 