5.3.6. Fire Alarm
This menu is used to define the contact inputs functionality. Contacts are used to assign EVAC and
ALERT messages, Built‐in‐music general messages, or INPUT 1‐6 to the outputs.
The first step is to configure the Alarm mode. There are three possible options:
-
All zone: Messages or Line inputs are assigned to all zones. You cannot select them
individually.
-
Specify zone: Messages or Line inputs are assigned individual zones; you have to select them
in the bottom menu.
In these modes you have to select the Play mode, it can be Single Loop or List loop. This
parameter only affects pre‐recorded messages. Then select the HOST,
using and icons on the top, and the contact to set with
For each contact you have to select the mode Emergency or Business. In Emergency mode
Messages are broadcasted to all/specified zones at maximum volume, Emergency LED is
activated and Emergency buzzer sounds. In Business mode Emergency LED and buzzer is not
activated and audio is affected by MASTER volume
You can select with Automatic release after triggering event evacuation if system comes
back to previous status after the event, otherwise, in case of Emergency mode you have to
press EMERGENCY button in the front panel, or activate Emergency Reset contact in the
rear panel, to finish Emergency mode.
NOVA Version 1.0
NOVA
Voice Evacuation System
using
icons on the right.
Page 22 of 34