Power supply 230 Vac 60/50 Hz - external to the control panel
- (120V/60Hz upon request)
J2
COM.
Common contact
CLOSE
Closing impulse contact (NA)
OPEN
Opening impulse contact (NA)
STOP
STOP impulse contact (NC)
AERIAL
Radio Antenna
SIGNAL
Gate open state and battery state output indicator (24Vdc 3W
max)
J3
A+TEST
+ 24Vdc safety strip self-test power supply
EDGE N.C.
Safety strip contact (NC)
COM.
Common contact
PHOTO N.C.
Photocells contact (NC)
K BUTT.
Single pulse contact (NO)
PED. BUTT.
Pedestrian opening contact (NA)
A+
+ 24Vdc accessories power supply
A -
- 24Vdc accessories power supply
LOCK
Electric lock connection (MAX 15W 12V)
- 24Vdc blinker (code ACG7061) power supply. Pay attention
to the polarity.
J4
SECONDARY
Connection to secondary coil of transformer 18 Vac
TRANSFORMER
J5
MOTOR 1
MOTOR 1 CONNECTION (without polarity)
J6
MOTOR 2
MOTOR 2 CONNECTION (without polarity)
J7
Connector dedicated to the factory programming. DO NOT
REMOVE ANY JUMPER! OTHERWISE THE OPERATOR WILL
NOT WORK!
SW T24 2V
J8
Connector dedicated to the factory programming (only CRX
control board) DO NOT REMOVE ANY JUMPER! OTHERWISE
THE OPERATOR WILL NOT WORK!
SW RADIO
J9
RADIO
Built-in radio module (model CRX), or connector for radio
receiver RIB, 24 Vdc supply
J10
BATTERY
Connector for charge card of 24Vdc battery (code ACG4648)
CHARGER
TR1
TRIMMER RUN
Trimmer for high speed adjustment operations
TR2
TRIMMER LOW
Trimmer for low speed adjustment operations
SPEED
TR3
TRIMMER TCA
Trimmer for automatic closing time adjustment (DISABLED
DEFAULT AND DL6 LED OFF)
S3
PROG
Programming button
B - SETTINGS
DIP 1
(ON) - MOTOR ROTATION DIRECTION CONTROL (POINT C)
DIP 2
(ON) - TIMER (POINT D)
DIP 3
(ON) - ACTIVATES DOOR RELEASE DURING PHASES OF SLOWDOWN AND
TOTAL OPENING AND CLOSING (AS PER THE IMPACT TESTS OF EN12453)
DIP 1-2 MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR TOTAL
OPENING (ONLY MODEL CRX) (POINT E)
DIP 1-3 MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR
PEDESTRIAN OPENING (ONLY MODEL CRX) (POINT F)
DIP 2-1 MICRO-SWITCH CONTROLLER FOR PEDESTRIAN OPENING TIMER
DIP 4
Photocells always active (OFF) - Photocells active only during closing (ON)
DIP 5
Pre-blinking (ON) - Normal blinking (OFF)
DIP 6
Single pulse command (K BUTT) and step-by-step radio receiver (OFF) - automatic
(ON)
DIP 7
Power sensor operation (ON-activated) time operation (OFF-activated).
DIP 8
Electric lock activation (ON-activated)
DIP 9
Electric lock pulse release (ON-activated)
DIP 10 Electric lock pulse engagement (ON-activated)
DIP 11 Easy release activation (ON-activated)
DIP 12 Sensor TEST activation (ON-activated).
DIP 13 Selection of 1 or 2 motor operation (default OFF 2 motors)
DIP 14 Selecting sensitivity to the impact
A - CONTROL PANEL FEATURES
J2
J9
J10
J8
J7
S3
FUSE 1 T 8 A
Motor protection fuse
F1
T 2 A
Transformer protection fuse
BRIDGE
Connecting bridge rectifier
DIP 15 Selecting sensitivity to the impact
DIP 14
DIP 15
Selecting sensitivity to the impact
OFF
OFF
HIGH (maximum protection)
ON
OFF
MEDIUM HIGH
OFF
ON
MEDIUM LOW
ON
ON
LOW (suggested in case of wind)
DIP 16
IMMEDIATE CLOSING AFTER PASSING IN FRONT OF PHOTOCELLS
ON
ACTIVATED
OFF
DEACTIVATED
JP1 => Check that the jumper is inserted!
JP2 => Check that the jumper is inserted!
JP3 => Check that the jumper is inserted!
PROG => S3 Programming button
ADJUSTMENTS
ATTENTION: PUT DIP 3 IN THE ON MODE ONLY AFTER HAVING CARRIED OUT ALL THE
PROGRAMMING PROCEDURES.
NOTE: WITH DIP 3 (ON) BRIEF GATE REVERSAL AFTER IMPACT IS ACTIVATED.
THIS BRIEF GATE REVERSAL PERMITS STATIC FORCE TO BE REDUCED TO ZERO