Electric connections (standard models)
Power supply and control wiring

Ensure that the voltage indicated on the actuator ID label corresponds to the voltage supply.

Unscrew the left cable gland and insert the cable.

Remove 25mm of the cable sheath and strip each wire by 8mm.

Connect the wires to the terminal strip in accordance with the diagram p. 33.

Tighten the cable gland (Ensure that it's well mounted to guaranty the proofness).
The actuator is pre-set in our factory. Do not touch the two lower cams in order to avoid any malfunctioning or
even damage to the actuator.
Position feedback wiring

Unscrew the right cable gland and insert the cable.

Remove 25mm of the cable sheath and strip each wire by 8mm.

Connect the wires to the terminal strip in accordance with the diagram p. 33.

Tighten the cable gland (Ensure that it's well mounted to guaranty the proofness
Our actuators are equipped with two simple limit switch contacts normally set either in open position, either in closed
position (see DSBL0470 wiring diagram inside the cover). As per factory setting, the white cam is used to detect the open
position (FC1) and the black cam is used to detect the closed position (FC2).
To adjust the position of the auxiliary contacts, make rotate the two superior cams by using the appropriate wrench.
32
EN
DSBA3800 • Rév. 01/10/2020