Control and safety devices

13 CONTROL AND SAFETY DEVICES

Compressor protection

The compressor is protected by the following devices and their combinations:
1 Pressure switch: this switch stops the compressor when the discharge pressure exceeds the set value.
2 Oil heater: this band-type heater protects against the formation of foam on the oil during cold starts and remains enabled when the
compressor is at a standstill.
Model
For Compressor
Pressure Switches
Cut-Out
High
Cut-In
Fuse Capacity
3N~ 400V 50Hz
Oil Heater
Capacity
CCP Timer
Setting Time
For DC Fan Module
Fuse Capacity
3N~ 400V 50Hz
Model
For Compressor
Pressure Switches
Cut-Out
High
Cut-In
Fuse Capacity
3N~ 400V 50Hz
Oil Heater
Capacity
CCP Timer
Setting Time
For DC Fan Module
Fuse Capacity
3N~ 400V 50Hz
73
PMML0294A_rev.2_02-2014.indb 73
RAS-8FSXN1E
-0.05
MPa
4.15
-0.15
MPa
3.20 +0.15
A
40 x 2
W
40.8 x 2
min.
3
A
20 x 1
RAS-5FSXNH(E)
-0.05
MPa
4.15
-0.15
MPa
3.20 +0.15
A
40 x 2
W
40.8 x 2
min.
3
A
20 x 1
PMML0294A rev.2 - 07/2014
RAS-10FSXN1E
RAS-12FSXN1E
Automatic Reset, Non-Adjustable
(each one for each compressor)
-0.05
-0.05
4.15
4.15
-0.15
-0.15
3.20+0.15
3.20+0.15
40 x 2
40 x 2
40.8 x 2
40.8 x 2
Non-Adjustable
3
3
20 x 1
20 x 1
RAS-6FSXNH(E)
RAS-8FSXNH(E) RAS-10FSXNH(E) RAS-12FSXNH(E)
Automatic Reset, Non-Adjustable
(each one for each compressor)
-0.05
-0.05
4.15
4.15
-0.15
-0.15
3.20+0.15
3.20+0.15
40 x 2
40 x 2
40.8 x 2
40.8 x 2
Non-Adjustable
3
3
20 x 1
20 x 1
RAS-14FSXN1E
RAS-16FSXN1E
-0.05
-0.05
4.15
4.15
-0.15
-0.15
3.20+0.15
3.20+0.15
40 x 2 + 32 x 3
40 x 2 + 32 x 3
40.8 x 4
40.8 x 4
3
3
20 x 1
20 x 1
-0.05
-0.05
4.15
4.15
-0.15
-0.15
3.20+0.15
3.20+0.15
40 x 2
40 x 2
40.8 x 2
40.8 x 2
3
3
20 x 1
20 x 1