Piping work and refrigerant charge

8 PIPING WORK AND REFRIGERANT CHARGE
8.1 REFRIGERANT PIPE SELECTION
8.1.1 Refrigerant pipe selection
The RAS-(8-54)FSXN1E(-P) and RAS-(5-36)FSXNH(E)(-P) out-
door units can work as a heat pump system, by means of a two-
pipe system (gas pipe and liquid pipe), or they can work as a heat
recovery system by means of a three-pipe system (high and low
pressure pipes and liquid pipe), requiring in addition the CH units
supplied as accessories.
There is an optional specific pipe connection kit available accord-
ing to the power of the outdoor unit:
Operating
Outdoor unit
mode
(16-P)(18-24)
(26-32)
(32-P)(34-48)
Heat
(50-54)
pump
system
(12-P) (14-24)
(24-P) (26-36)
(16-P)(18-24)
(26-32)
(32-P)(34-48)
Heat
(50-54)
recovery
system
(12-P) (14-24)
(24-P) (26-36)
8.1.2 Copper pipes, sizes, connection and insulation

Copper pipes and sizes
C A U T I O N
The copper pipe used in the refrigeration installations is different to the copper pipe used in installations carrying domestic or
heating water.
The copper pipe for refrigeration installations is especially treated for outdoors and indoors. The interior surface finish makes it
easier for the refrigerant to circulate and withstands the action of the lubricant oil applied to outdoor equipment.
Prepare the copper pipes provided by the supplier.
Select the pipe with the appropriate diameter and thickness. Use the table below to select the most appropriate pipe:
Nominal diameter
mm
Inches
ø6.35
1/4
ø9.52
3/8
ø12.7
1/2
ø15.88
5/8
ø19.05
3/4
ø22.2
7/8
20
PMML0294A_rev.2_02-2014.indb 20
Nº of
Connection
outdoor
Indications
kit
units
2
MC-20AN1
2
MC-21AN1
2 pipes type
3
MC-30AN1
for high/low
4
MC-40AN1
pressure
gas
2
MC-20AN1
for liquid
3
MC-30AN1
2
MC-20XN1
3 pipes type
2
MC-21XN1
for high/low
3
MC-30XN1
pressure
4
MC-40XN1
gas
for low
2
MC-20XN1
pressure gas
for liquid
3
MC-30XN1
Thickness mm
Supply
0.80
Coil
0.80
Coil
0.80
Coil
1.00
Coil
1.00
Straight lenghts
1.00
Straight lenghts
PMML0294A rev.2 - 07/2014

Pipe size selection
Select the pipe size in line with the following instructions:
1 Between the outdoor unit and the branch pipe (multikit): se-
lect the same pipe connection size as for the outdoor unit.
2 Between the branch pipe (multikit) and the indoor unit: select
the same pipe connection size as for the indoor unit.
C A U T I O N
Do not use refrigerant pipe sizes other than those indicated
in this manual. The diameter of the refrigerant pipes depends
directly on the power of the outdoor unit.
If larger diameter refrigerant pipes are used, the circuit lubri-
cation oil tends to separate from the gas carrying it. The com-
pressor will be seriously damaged due to a lack of lubrication.
If smaller diameter refrigerant pipes are used, the gas or liquid
refrigerant will have serious difficulties in circulating. System
performance will be affected. The compressor will run under
more severe conditions than foreseen and will be damaged in
a short space of time.

Multikit or distributor selection
N O T E
Pipe connection sizes on outdoor units, indoor units and the
multikit or distributor vary depending on the system. Consult
the Service Manual for the SET FREE Series FSXN1E and
FSXNH(E).
The sizes of the indoor and outdoor units are different. Adjust
the flare adapter (accessory) to the indoor pipe connection.
Nominal diameter
mm
Inches
ø25.4
1
ø28.58
1-1/8
ø31.75
1-1/4
ø38.1
1-1/2
ø41.3
1-5/8
ø44.45
1-3/4
Thickness mm
Supply
1.00
Straight lenghts
1.00
Straight lenghts
1.10
Straight lenghts
1.35
Straight lenghts
1.45
Straight lenghts
1.55
Straight lenghts
14/07/2014 12:28:10