Electric diagram

ALIMENTATION
N
Ph
-
+
1
2
TP/PE
100V-240V 50/60Hz (100V-350V DC)
24V-30V 50/60Hz (24V-48V DC)
1,2,3,4
Power supply terminal
67,68
Failure report Terminal (24V DC / 3A max)
A,0,B
RS485 terminal
13a,13b,14
Feedback signal terminal 4-20 mA (13b) or 0-10 V (13a)
The card resolution is 1°
In order to avoid electromagnetic perturbations, it's mandatory to use shielded cables (cables longer than 3m).
The control voltage must be S.E.L.V. (Safety Extra Low Voltage).
No common earth/ground connexion between the control (input and output signal) and the alimentation. (Type
0-20 or 4-20mA : 5V DC max.)
10 kOhm input impedance if control with voltage (0-10 V) and 100 Ohm input impedance if control with current
(0-20 mA or 4-20 mA)
8
3
4
17
18
C
17
18
16 +
15 -
13a +
13b +
14 -
A
~
+
~
B
Motor
=
A
SNBA150000
4,5
Auxiliary limit switch 1 NO
6,7
Auxiliary limit switch 2 NO
15,16
Setpoint signal terminal 4-20 mA or 0-10 V
FEEDBACK
4
5
6
7
8
SNAA690000
67
68
A
0
B
DSBA3307 • Rév. 16/04/2021
EN