Mod.
CODE
1
DY350T
2
DY400T
3
DY550T
•
Use a connecting cable type H07 of a suitable electrical section for the consumed intensity by
the pump motor.
•
Before connecting the motor, check the necessary fuse type.
•
Adjust the correct thermical value according to the needs of each pump.
•
Verify the right connection of the ground cable to the installation.
•
It is very important to keep to the installation and electrical connection conditions. Should they
not be heeded, the pump manufacturer does not accept any responsibility and considers the
guarantee void.
•
The motors are subject to ECC regulations with IP-55 protection.
•
Special installation regulations may exist.
•
The main cable can only be connected by qualified and authorised personnel (Type three-phase
connection).
•
Incorrect mains connection could result in death.
4. START-UP INSTRUCTIONS
QUESTIONS PRIOR TO START-UP
•
Before starting up the pump, carry out the following operations:
1. Open the pre-filter cover (See Fig.4).
2. Fill the pump with water through the pre-filter until it dips into the suction tube.
HEAT PROTECTOR TABLE
V.
HP
230/400
3
230/400
4
230/400
5.5
kW
Intensity relay regulation (A)
2.2
2.9
4
32
8 / 4.8
12.6 / 7.3
14.9 / 8.6