COnsTrUCTiOn sPeCifiCATiOns
Distortion of input current at 100%
of nominal load
Input power factor
Overload current
Number of input phases
Line fuse
Battery charger direct from mains
Output wave form
With mains operation
With battery operation
Type of operation
electrical output specifications with mains operation
Nominal output voltage
Nominal output frequency
Output current with linear load PF=0,7
Tolerated crest factor on output current
Nominal output power
Active output power with linear or
non-linear load PF=0,7
Total harmonic distortion of output voltage
with linear nominal load
Total harmonic distortion of output voltage
with non-linear nominal load PF=0,7
Overload capacity
Whad 0.8, 1, 1.5 kVA
3 100 87
3 100 90
3 100 88
3 100 91
3 100 89
3 100 92
<3%
>0.99 at 80% of nominal load from 20%
to 100% of nominal load
100% of nominal current
Single phase
Automatic Resettable 10 A
Deeply discharged batteries are recharged in
12 to 15 hours when mains power is present,
even should the UPS not be operating.
Sinewave
Sinewave
No break, on line UPS with passing neutral
and double conversion
230V stepwise setting with step of 1V in the
range of 184V to 255V
50Hz/60Hz synchronized
3,5 Arms
4,4 Arms
3,5
3,5
800 VA
1000 VA
560 W
700 W
< 0,5%
< 1%
300% for at least 1 second without bypass
intervention
200 % for at least 5 seconds without bypass
intervention
150% for at least 30 seconds without bypass
intervention
3 100 93
3 100 94
3 100 95
6,6 Arms
3,5
1500 VA
1050 VA
27