12. Specifications
Output signal (4 ... 20 mA version)
Factory configuration
Measuring range
EN
Current signals for
error signalling
Current value for
sensor short-circuit
Communication
Info data
Configuration and
calibration data
Configuration software WIKAsoft-TT
Voltage supply
Supply voltage U
Supply voltage input
Permissible residual
ripple of supply voltage
Time response
Switch-on delay,
electrical
Warm-up time
30
Measuring range 0 ... 150 °C [32 ... 302 °F]
Other measuring ranges are adjustable
Configurable in accordance with NAMUR NE 043
downscale ≤ 3.6 mA
upscale ≥ 21.0 mA
Not configurable in accordance with NAMUR NE 043
downscale ≤ 3.6 mA
Tag no., description and user message can be stored
in transmitter
Permanently stored
→ Configuration software (multilingual) as a
download from www.wika.com
DC 10 ... 30 V
B
Protected against reverse polarity
10 % generated by U
current
Max. 4 s (time before the first measured value)
After approx. 4 minutes, the instrument will function
to the specifications (accuracy) given in the data
sheet.
WIKA operating instructions model TR33
< 3 % ripple of the output
B