PIXIT for GOOSE publish model
ID
Ed
Description
Gp1
1,2
Can the test (Ed1) / simulation (Ed2) flag in the
published GOOSE be set
Gp2
1
What is the behaviour when the GOOSE publish
configuration is incorrect
Gp3
1,2
Published FCD supported common data classes
are
Gp4
1,2
What is the slow retransmission time
Is it fixed or configurable
Gp5
1,2
What is the fastest retransmission time
Is it fixed or configurable
Gp6
-
Can the GOOSE publish be turned on / off by
using SetGoCBValues(GoEna)
Gp7
1,2
What is the initial GOOSE sqNum after restart
Gp8
1
May the GOOSE data set contain:
- structured data objects (FCD)
- timestamp data attributes
<additional items>
Value / Clarification
N
If goose pdu is too large
NdsCom=True and DUT keeps
GoEna=False
If no DatSet is configured
NdsCom=True and DUT keeps
GoEna=False
CIDs with incorrect goose publish
configuration are rejected
Any FCD with FC=ST/MX/SP
Arrays are not supported
Max value: 2.147.483.647 ms
Configured by GoCB MaxTime
Default value: 2000 ms
Min value: 2ms
Configured by GoCB MinTime
Default value: 2ms
Deprecated
See PICS - SetGoCBValues
1
Y
Y
8