ZIV ZLF Serie Manual De Instrucciones página 804

Protección de distancia
ID
Ed
Description
Sr5
1
Which Mode values are supported
<additional items>
PIXIT for Data set model
ID
Ed
Description
Ds1
1
What is the maximum number of data elements in
one data set (compare ICD setting)
Ds2
1
How many persistent data sets can be created by
one or more clients
(this number includes predefined datasets)
Ds3
1
How many non-persistent data sets can be created
by one or more clients
<additional items>
PIXIT for Setting group control model
ID
Ed
Description
Sg1
1
What is the number of supported setting groups
for each logical device
Sg2
1,2 What is the effect of when and how the non-
volatile storage is updated
(compare IEC 61850-8-1 $16.2.4)
Sg3
1
Can multiple clients edit the same setting group
Sg4
1
What happens if the association is lost while
editing a setting group
Sg5
1
Is EditSG value 0 allowed
Sg6
2
When ResvTms is not present how long is an edit
setting group locked
<additional items>
IEC 61850-6:2009 clause 9.5.6 states that if only a subrange of the enumeration value set is supported, this shall be indicated within an ICD file by an
1
enumeration type, where the unsupported values are missing
Value / Clarification
On
1
[On-]Blocked
Test
Test/Blocked
Off
The supported Mode values are
indicated by using different
enumeration types for each case.
Value / Clarification
Fixed in ICD to 500
0
0
Value / Clarification
8
If values are updated in a CID,
these changes take effect after
starting up.
If values are updated by MMS
services, these changes take effect
immediately
N
The EditSG is reset to 0
Y
ResvTms is present. Its default
value is 3600 seconds
Y
Y
N
N
Y
4