Capítulo 6. Supervisión y Control
6.4.9
Nodo lógico IEC 61850
Data Object
Common Data Class
Name
LNName
Data Objects
Status information
Rel
SPS
VInd
SPS
AngInd
SPS
HzInd
SPS
Settings
DifV
ASG
DifHz
ASG
DifAng
ASG
LivLinVal
ASG
LivBusVal
ASG
BrkTmms
ING
Extended Data
VStChkOk
EXT_SPS
LivLin
EXT_SPS
LivBus
EXT_SPS
SynIn
EXT_SPS
SynEx
EXT_SPS
Vsyn
EXT_CMV
HzSync
EXT_MV
LNInSvc
EXT_SPG
SynMod
EXT_ENG
VMod
EXT_ENG
VCorFact
EXT_ASG
VsupEna
EXT_SPG
DifVEna
EXT_SPG
DifAngEna
EXT_SPG
DifHzEna
EXT_SPG
OpDlTmms
EXT_ING
FuFailBlkE
EXT_SPG
CbTmComp
EXT_SPG
DeaADeaB
EXT_SPG
DeaALivB
EXT_SPG
LivADeaB
EXT_SPG
LivALivB
EXT_SPG
CLASS ZLFRSYN
Explanation
The name shall be composed of the class name, the LN-Prefix
and LN-Instance-ID according to IEC 61850-7-2, Clause 22
Release. Synchrocheck close permission
Voltage difference permission indication
Angle difference permission indication
Frequency difference permission indication
Difference voltage
Difference frequency
Difference angle
Live Line Value
Live Bus Value
Closing time of breaker
Both sides energization permission
Voltage presence in line
Voltage presence in bus
Internal calculated synchrocheck permission
External synchrocheck permission
Synchrocheck channel voltage
Synchrocheck channel frequency
In service
Synchrocheck Mode (internal/external)
Type of voltage in bus side
Voltage compensation factor
Enable supervision at both sides of breaker
Enable voltage difference
Enable angle difference
Enable frequency difference
Time delay
Enable synchrocheck block due to fuse failure
Enable breaker close time compensation
Enable energization mask dead A, dead B
Enable energization mask dead A, live B
Enable energization mask live A, dead B
Enable energization mask live A, live B
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2018
M0ZLFA1807E
6.4-12
ZLF: Protección de Distancia