Nodos Lógicos Iec 61850 - ZIV ZLF Serie Manual De Instrucciones

Protección de distancia
Capítulo 3. Unidades de Protección de Intensidad
3.6.9
Nodos lógicos IEC 61850
Data Object
Common Data
Name
LNName
Data Objects
Status information
Str
ACD
OpEx
ACT
OpIn
ACT
Settings
SP1F1Tmms
ING
FailTmms
ING
NLodFlTmms
ING
SP1TrTmms
ING
TPTrTmms
ING
NLodTrTmms
ING
SP1DetValA
ASG
DetValA
ASG
DetValAGnd
ASG
Extended Data
LNInSvc
EXT_SPG
StrSup
EXT_SPG
StrSP1
EXT_ACD
StrTP
EXT_ACD
StrGnd
EXT_ACD
ExTPStrIn
EXT_SPS
ExP1StrIn
EXT_SPS
ExP2StrIn
EXT_SPS
ExP3StrIn
EXT_SPS
RsMem
EXT_SPC
CBPosStrIn
EXT_SPS
GndStrIn
EXT_SPS
OpExMem
EXT_ACT
CLASS RBRF
Class
The name shall be composed of the class name, the LN-Prefix
and LN-Instance-ID according to IEC 61850-7-2, Clause 22
Start
Trip
Retrip
Delay time single-phase
Delay time three-phase
Delay time three-phase no load
Sigle pole retrip time delay
Three pole retrip time delay
Three pole no load retrip time delay
Current detector value for single-phase
Current detector value for three-phase
Current detector value for ground
In service
Pickup Supervision
Pickup of the single phase BF unit
Pickup of the three phase BF unit
Pickup of the ground BF unit
Three-phase external Protection trip
Single-phase A external Protection trip
Single-phase B external Protection trip
Single-phase C external Protection trip
Memorized breaker failure reset
No Load Breaker failure contact position start
No Load Breaker failure ground unit start
Memorized breaker failure
Explanation
ZLF: Protección de Distancia
 ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2018
M0ZLFA1807E
3.6-12
loading