08: Bypass frequency range setting
Interfaz
ES
09: Salidas programables activado / desactivado
Interfaz
10: Configuración de salidas programables
Interfaz
11: Configuración del tiempo de autonomía para las tomas generales
Interfaz
Impostación
Parameter 2 & 3: Set the acceptable high frequency
point and acceptable low frequency point for Bypass mode
by pressing the Down key or Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz
to 55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz
to 65Hz(Default: 63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz
to 49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz
to 59Hz(Default: 57.0Hz)
Impostación
Parámetro 3: Activar o desactivar las salidas
programables.
ENA: Salidas programadas facultada
DIS: Salida previstas son discapacitados
Impostación
Parámetro 3: Fijar plazos para la copia de seguridad de
los productos programables.
0-999: ajuste de la hora normal de la autonomía de las
cargas. 0-999 durante unos minutos de autonomía para no
cargas críticas, con el funcionamiento del SAI en modo de
batería.
Configuración
Parametro 3: Configura el tiempo de autonomía en modo
batería para las tomas generales (para dispositivos críticos).
0-999: ajusta el tiempo de autonomía (durante el modo
batería) de 0 a 999 minutos para las salidas generales
0: Cuando se fija "0", el tiempo de autonomía serán 10 seg.
DIS:
Disable the autonomy limitation and the backup
time will depend on battery capacity. (Standard)
12
(Standard)