PowerWalker 1000 LCD Manual De Instrucciones página 16

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
11: Autonomy limitation setting
Interface
12: Battery total AH setting
Interface
13: Charger maximum current setting
Interface
14: Charger Boost voltage setting
Interface
15: Charger Float voltage setting
Interface
00: Exit setting
Setting
Parameter 3: Set up backup time on battery mode for
general outlets.
0-999: setting the backup time in minutes from 0-999 for
general outlets on battery mode.
0: When setting as "0", the backup time will be only 10
seconds.
DIS: Disable the autonomy limitation and the backup time will
depend on battery capacity. (Standard)
Setting
Parameter 3: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
Setting
Parameter 3: Set up the charger maximum current.
1/2/4/6/8: setting the charger maximum current
1/2/4/6/8* in Ampere. (Default: 8A)
*Note: This setting is only available for super charger.
Setting
Parameter 3: Set up the charger boost voltage.
2.25-2.40: setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
Setting
Parameter 3: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)
13
EN
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

1500 lcd2000 lcd3000 lcd

Tabla de contenido