PowerWalker 1000 LCD Manual De Instrucciones página 61

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
08: Bypass frequency range setting
Interface
FR
09: Activation/désactivation des sorties programmables
Interface
10: Configuration des sorties programmables
Interface
11: Configuration des prises générales.
Interface
Valeur
Parameter 2 & 3: Set the acceptable high frequency point
and acceptable low frequency point for Bypass mode by
pressing the Down key or Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz to
55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz to
65Hz(Default: 63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
Valeur
ENA : active les sorties programmables
DIS : désactive les sorties programmables (Standard)
Valeur
0-999 : réglage de l'autonomie en minutes de 0 à 999 pour
les prises sorties programmables connectées aux charges
non-prioritaires en mode Batteries.
(Default: 999)
Valeur
Paramètre 3: Réglage de l'autonomie des prises générales
en mode batterie.
0-999: Réglage du temps d'autonomie en minutes de 0-999
pour les sorties génerales en mode batterie.
DIS: Disable the autonomy limitation and the backup time
will depend on battery capacity. (Standard)
0: Quand la valeur est "0", le temps d'autonomie est de 10
secondes.
12
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

1500 lcd2000 lcd3000 lcd

Tabla de contenido