♦ Refrigerant cannot be charged until field wiring has been completed.
♦ Refrigerant may only be charged after performing the leak test and the vacuum pumping.
♦ When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.
!
CAUTION
♦ Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the
appropriate refrigerant is charged.
♦ Refrigerant containers shall be opened slowly.
♦ Always use protective gloves and protect your eyes when charging refrigerant.
■ The outdoor unit is factory charged with refrigerant R410A. Calculate the added refrigerant according to the diameter and
the length of the liquid side pipe of the outdoor unit/indoor unit connection.
No added refrigerant when the length L(m) is less than 5m
Added refrigerant when the pipe length L(m) is over than 5m

5.8. Electrical connection between indoor and outdoor units

♦ The appliance shall be installed in accordance with national wiring regulations.
♦ The air conditioner should use separate power supply with rated voltage.
♦ The external power supply to the air conditioner should have ground wiring, which is linked to the ground
wiring of the indoor and outdoor unit.
♦ The wiring work should be done by qualified persons according to circuit drawing.
!
CAUTION
♦ An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual
current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according to
the national rule.
♦ Be sure to locate the power wiring and the signal wiring well to avoid cross-disturbance.
♦ Do not turn on the power until you have checked carefully after wiring.
NOTE: Remark per EMC Directive 89/336/EEC For to prevent flicker impressions during the start of the compressor
(technical process), following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. The distribution has to be of
low impedance; normally the required impedance reaches at a 32A fusing point.
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance please refer to your power supplier, if restrictions do apply for products like washing
machines, air conditioners or electrical ovens.
4. For power details of the air conditioner refer to the rating plate of the product.
5. For any question contact your local dealer.
- Connect the wire
1. Remove the electric parts cover from the outdoor unit.
2. Insulate unused cords (conductors) with PVC-tape. Process them so they do not touch any electrical or metal parts.
37
Connective pipe length
Additional refrigerant to be charged
-----------
(L-5m)X15g