8.2 Modbus IF-Module
Set data format with parameter C in the pump menu 5.2.5.0 in accordance with
the following table:
Parameter C
2
3
6
10
* N – no parity, E- even parity, O – odd parity
All other settings are reserved for expansions (see also the protocol description).
8.3 BACnet IF-Module
The BACnet instance number is set with the parameters
C (in the pump menu 5.2.5.0)
E (in the pump menu 5.2.6.0)
F (in the pump menu 5.2.7.0)
This requires conversion into a hexadecimal value
by an 'h' suffix).
The instance number is divided between the three parameters (example 4660):
1)
For example with the calc.exe program in the scientific view
Installation and operating instructions Wilo-IF-Modules Modbus, BACnet
Parity*
Data bits
N
8
N
8
S
8
O
8
Stop bits
1
2
1
1
1
) (indicated in the following