Option 37 - Set time duration of override rule
GB
(Option 36 set to 1 or 2)
This establishes the duration of a temperature
override available to the user. Press + until Option
37 is displayed, use V and Λ to select required
setting.
Setting 0 Next event (factory setting)
Setting 1 1 hour
Setting 2 2 hours
Setting 3 3 hours
Setting 4 4 hours
Option 38 - Relay state on low battery detect
(battery products only)
This establishes the position that the relay is driven
to when the unit shuts down due to low battery
state. Press + until Option 38 is displayed, use
Λ
to select required setting.
Setting 0 Relay parked with output OFF (factory setting)
Setting 1 Relay parked with output ON
Option 40 - Number of Events per Day
This sets the thermostat to operate with either 2,
4 or 6 switching events per day or to run it in stat
mode. Press + until option 40 is displayed, use Λ or
V to select required setting.
1
2
4
6
10
Stat mode
Two switching events per day
Four switching events per day
Six switching events per day (Factory setting)
V
and