Danfoss TP5001 Serie Instrucciones De Instalación página 13

Ocultar thumbs Ver también para TP5001 Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 26
Option 93 - Set limit sensor set-point, "A" models only,
(option 90 set to 2)
This allows the thermostat limit sensor to be set,
typical application is fl oor htg. Press + until Option
93 is displayed, use V and Λ to select required
setting. If the temperature sensed by the limit
sensor exceeds the limit setting the output will be
turned off untill the temperature has dropped by
2°C "F10" will fl ash in the display.
Setting
Any value between 20 - 50°C (Factory setting is 27°C)
Option 94 - Confi gure digital input switch type, "A" models only,
(option 90 set to 3)
This allows switch type of digital input to be
confi gured. Press + until Option 94 is displayed, use
V and Λ to select required setting.
Setting 0 Contacts NC, open circuit contact to force unit into
thermostat mode, short circuit contacts to return to normal
operation
Setting 1 Contacts NO, short circuit contacts to force unit into
thermostat mode, open circuit contacts to return to normal
operation (Factory setting)
GB
13
Tabla de contenido
loading

Este manual también es adecuado para:

Tp5001Tp5001aTp5001-rfTp5001mTp5001ma

Tabla de contenido