12: Neutral loss detection Interface:
Display
13: Calibrate the battery voltage Interface
14: Adjust charger voltage Interface
NOTE * :
*Before making voltage adjustment, be sure to disconnect all batteries first to get the accurate charger
voltage.
*We strongly suggest to use the default value (0). Any modification should be suitable to battery specifications.
ON-LINE RACK
Parameter 2:
Enable or disable Hot standby function. You may choose following two
options in P arameter 2:
YES: Hot standby function is enabled. It means that the current UPS is
set to host of the hot standby function, and it will restart
after AC recovery even without battery connected.
N O: Hot standby function is disabled. The UPS is running
mode and can't restart without battery
After it shows "13" in parameter 1, please press "Enter" key first. Then, you
may choose Ad or S U to adjust battery voltage in
parameter 1 by pressing "Up" or "Down" key. After pressing
"Enter" key to confirm your selection, it will jump to parameter 2 to set up
the value.
Parameter 2 : the voltage range is from 0V to 5.7V, the default value is 0V.
After it shows "14" in parameter 1, please press "Enter" key first. Then, you
may choose A d or S U to adjust charger voltage in
parameter 1 by pressing "Up" or "Down" key. After pressing "Enter" key to
confirm your selection, it will jump to parameter 2 to set up the value.
Parameter 2: the voltage range is from 0V to 9.9V, the default value is 0V.
Configuration
P H 9360 - PH 9301 .
at normal