08: Configuración modo bypass
Display
09: Setting the battery discharge time
10: Reserved
11: Reserved
ON-LINE RACK
After it shows "08" in parameter 1, please press "Enter" key first. Then,
you have the following options to choose in p arameter 1 . O P : Bypass
allowed. When selected, UPS will run at Bypass mode
depending on bypass enabled/disabled setting.
Fb: Bypass not allowed. When selected, it's not allowed for running in
Bypass mode under any situations.
After selecting "OP" in parameter 1, it's able to set up bypass condition in
parameter 2.
ENA : Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass means
users manually operate UPS for Bypass mode. For
example, pressing OFF button in AC mode to turn into Bypass
mode.
Parameter 3: 000 ~ 999: Sets the maximum download time: from 0 minutes
to 999 minutes. The UPS will shut down to protect the batteries when the
discharge time arrives before the batteries run out of voltage. The default
value is 990 minutes.
DIS: Deactivates battery discharge protection: the time will depend on the
capacity of the batteries.
Function reserved for future options
Function reserved for future options