05: Activate / Deactivate ECO Mode Interface Phasak UPS PH 9360 / PH 9301
06: Voltage range for ECO mode Interface Configuration
07: Frequency range for ECO mode Interface Configuration
ON-LINE RACK
Parameter 2: Enable or disable ECO function. You may choose
following two options:
DIS : disable ECO function
ENA : enable ECO function
If ECO function is disabled, voltage range and frequency range for ECO
mode still can be set, but it is meaningless unless the ECO function
is enabled.
Parameter 1 & 2: S etting acceptable voltage range for ECO mode.
You have to set up the range by setting high and low
points. When it shows "LLS" in parameter 2, please press "Enter" key and it
will show "LS" in parameter 1. Now, you can set up low
point in parameter 2 by pressing "Up" or "Down" key.
LS: L ow voltage point in ECO mode. The setting range is from 5% to 10%
of the nominal voltage.
Pressing "Enter" key to confirm the setting value for low point. Then, it will
show HS in parameter 1. Please set up high point in parameter 2 by
pressing "Up" or "Down" key.
HS: H igh voltage point in ECO mode. The setting range is from 5% to 10%
of the nominal voltage.
Parameter 1 & 2: Setting acceptable frequency range for ECO mode.
You
have to set up the range by setting high and low
points. When it shows "LLS" in parameter 2, please press "Enter"
key and it will show "LS" in parameter 1. Now, you can set up low point in
parameter 2 by pressing "Up" or "Down" key.
LS: S et low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz. 60 Hz
system: Setting range is from 56.0Hz to 58.0Hz. The default
value is 48.0Hz/58.0Hz.
Pressing "Enter" key to confirm the setting value for low point. Then, it will
show HS in parameter 1. Please set up high point in parameter 2 by
pressing "Up" or "Down" key.
HS : Set high frequency point for ECO mode. 50 Hz: Setting range is from
52.0Hz to 54.0 Hz. 60 Hz: Setting range is from 62.0Hz to 64.0Hz. The
default value is 52.0Hz/62.0Hz.