18
en
Terminal assignment
See drawing on page 4.
Labeling
Connection
Upper connections, from left to right
24 V +/-
Switch output +24 V max. 2.8 A (battery buffered, optional)
24 V +/-
Switch output +24 V max. 2.8 A (battery buffered, optional)
Lower connections, from left to right
MAIN +/-
Power supply unit connection
MAIN FAULT Signal input, power supply fault
BAT1 +/-
Battery pair 1 connection
BAT2 +/-
Battery pair 2 connection
FAULT AC -
Switch output, mains fault
FAULT BAT - Switch output, battery fault
FAULT Σ -
Switch output, collective fault
FAULT +24 V Switch output +
Standby current calculation in accordance with EN 54-4
Formula (1) gives the maximum panel current required to provide a specific
buffering time (I
Formula (2) gives the maximum panel current with simultaneous
consideration of the battery charge (I
According to formula (3), the required standby current of the panel (I
based on the smaller value of the two maximum current values of the panel.
Parameter:
-
t
= buffering time in hour
Standby
-
I
= maximum alarm current (I
Alarm
-
C
= battery capacity in Ah
Batt
The following capacities are feasible:
-
24–26 Ah and 36–45 Ah for 2 batteries
-
48–52 Ah and 72–90 Ah for 4 batteries
F.01U.081.382 | 3.0 | 2009.07
).
max,Standby
).
max,A
)
max,B
Bosch Sicherheitssysteme GmbH
BCM-0000-B
) is
nom