7. Electrical
work
<Example>
(In case of 2-branch
boxes)
Branch boxM
(5-branchtype)
[-- .....
TB3A--I
D , F_ln-d°°rLnit
Outdoor unit
,
_,l-t_;!
f:_1
I
A ROOM
rq
!
_/
.......
_i
:_t
® _
_bl
I
Circuit
'
'
r_CG-_l t C,
it TB2B
TB3B I
F-_-_-_
breaker
I
I_l
p q
L_
d£-1 i -(D_, '
£1%
B ROOM
i
____,,
,
_
,
___'___ =
_--i
cROOM
IE
°ROOM
II
:
,-4q--
D
I--=_=:-I
(C) I I
I'_
I
E ROOM
i....
@
i
'-11-
_',
_1
IL .......
,
I I
..........
Indoor unit
i i
TB3A I ,_,
I-- ....
I I
I FROOM
IL
:
I I
TB3B I
r-- ....
I I
TB2B
_
I
G ROOM
IIL
I li
TB3C I
r-- ....
,
I
H ROOM
,,..... _o__j
L£_:
Branch box_2
(3-branch type)
Fig. 7-3
7.3. External wiring procedure (Fig. 7-3)
The power supply work is needed only to the outdoor unit. The power supply to the
branch box or indoor unit is conducted
through wiring.
Therefore,
the power supply work can be carried out at just one spot of the outdoor
unit. It will contribute to simplifying
the work and saving costs.
® Power supply single phase
AC208/230
V, 60 Hz
Max. Permissive
System Impedance
0.22 (_)
Note:
(_ Power supply
input:
Outdoor
unit only.
Connect
the lines (C), (D) in accordance
with
the terminal
block
names to
ensure
correct
polarity.
Wire diameter
Breaker "1
(A) Main power (B) Ground
(C) Signal line (D) Signal line interrupting
Performance
line
current
characteristic
10.6 mm _
10.6 mm _
1.65 mm _
1.65 mm _
50 A, 30 mA for
5O A
AWG7
AWG7
AWG15 *2
AWG15 *2
0.1 sec. or less
Maximum circuit ampacity
Maximum rating of over-current protector device
32 A
52 A
When using twisted wire for the wiring, the use of round terminal is required.
• 1. A breaker with at least 3 mm [1/8"] contact separation in each pole shall be provided. Use
earth leakage breaker (NV).
•2. Max. 45 m (147 ft.) ("Outdoor unit - Branch box #1" plus "Branch box #1 - Branch box #2").
Notes:
1. Wiring sizes must comply
with the applicable
local and national code.
2. Use wires rated
600 V or more for the power
supply
cables
and the indoor
unit/branch
box/outdoor
unit connecting
cables.
3. Install
ground
wires longer
than power
cables.
4. Use separate
conduit
holes for power lines (3 lines) and signal lines (4 lines).
5. The inner diameter
of a wiring
conduit
for the power
line is required
to be
more than 10.1 mm (7/16").
6. Since the distances
between
the fixing
positions
of the grounds
for the sig-
nal lines and the terminal
blocks
for the signal
lines are long, the ground
wires for the signal
lines are 180 - 200 mm (7-1/16"
- 7-7/8") longer
than the
signal
lines.
7. Use copper
supply
wires.
Z_, Warning:
In case of A-control
wiring,
there
is high voltage
potential
on the S3 terminal
caused
by electrical
circuit
design
that has no electrical
insulation
between
power
line and communication
signal
line. Therefore,
please turn off the main power supply
when servicing.
And do not touch
the Sl, S2, S3 terminals
when the power
is energized.
If isolator
should
be used between
outdoor
unit and branch
box/indoor
unit and branch
box, please
use 3-pole type.
Power supply
Isolator (Switch)
$1
Outdoor unit $2
$3
3 poles isolator (Switch)
Sl
Sl _
................................
S2
Branch S2
box
S3
S3
"A-control"
$2
Indoor unit
$3
13