3. Installation
location
o
03
@
Fig. 3-1
i
Fig. 3-2
@
Fig. 3-3
mm (inch)
3.1. Refrigerant pipe
Refer to 5.2. Pipe length and height difference.
3.2. Choosing the outdoor unit installation location
• Avoid locations exposed
to direct sunlight
or other sources of heat.
• Select
a location
from which noise emitted
by the unit will not inconvenience
neighbors.
• Select a location permitting
easy wiring and pipe access to the power source and
indoor unit.
• Avoid locations
where combustible
gases may leak, be produced,
flow, or ac-
cumulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations
where the unit can be covered
by snow. In areas where heavy
snow fall is anticipated,
special
precautions
such as raising the installation
loca-
tion or installing a hood on the air intake must be taken to prevent the snow from
blocking the air intake or blowing directly against it. This can reduce the airflow
and a malfunction
may result.
• Avoid locations exposed
to oil, steam, or sulfuric gas.
• Use the transportation
handles of the outdoor
unit to transport
the unit. If the unit
is carried from the bottom, hands or fingers may be pinched.
3.3. Outline dimensions (Outdoor unit) (Fig. 3-1)
Constraints
on indoor unit installation
You should note that indoor units that can be connected
to this outdoor unit are the
following
models.
• Indoor units with model numbers
06, 09, 12, 15, 18, 24, 30 can be connected.
Refer to the table below for possible 2-8 room, indoor unit combinations.
Verification
The rated capacity should be determined
by observing the table below. The unit'
s quantities
are limited in 2 to 8 units. For the next step, make sure that the total
rated capacity selected will stay in a range of 12 - 70.2 kBTU/h.
Example:
MSZ-18 = 18
+
SEZ-12 = 12
+
SLZ-12 = 12
+
SEZ-09 =
9
+
SLZ-09 =
9
Total rated capacity
60 <170 kBTU/h
I
Indoor unit type
06
09
12
15
18
24
30
Ratedcapacty
Coo ng (kBTU/h
6
9
12
15
18
24
30
Combinations
in which the total capacity of indoor units exceeds the capacity of the
outdoor unit (= 54.0 kBTU/h) will reduce the cooling capacity of each indoor unit
below their rated cooling capacity. Thus, combine
indoor units with an outdoor unit
within the outdoor unit's capacity (= 54.0 kBTU/h), if possible.
3.4. Ventilation and service space
3.4.1. Windy
location
installation
When
installing
the outdoor
unit on a rooftop
or other location
unprotected
from
the wind, situate the air outlet of the unit so that it is not directly exposed
to strong
winds.
Strong wind entering the air outlet may impede the normal airflow and a malfunc-
tion may result.
The following
shows three examples
of precautions
against strong winds.
(_ Face the air outlet towards the nearest available
wall about 50 cm (19-11/16")
away from the wall. (Fig. 3-2)
Q Install an optional air guide if the unit is installed in a location where strong winds
from a typhoon, etc. may directly enter the air outlet. (Fig. 3-3)
@ Air guide
® Position the unit so that the air outlet blows perpendicularly
to the seasonal wind
direction, if possible. (Fig. 3-4)
® Wind direction