Operation
(continued)
resetting Your Inverter/Charger to restore AC Power
Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your
electrical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to "DC OFF" and remove some of the connected electrical load (i.e., turn off some of the
AC devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch back to
either "AUTO/REMOTE" or "CHARGE ONLY."
Output Circuit Breaker Reset: If tripped, remove a portion of the load, wait one minute and then press breaker button to reset.
Configuration
set Configuration DIP switches
Using a small tool, set the Configuration DIP Switches (located on the front panel, see diagram) to optimize Inverter/Charger operation
depending on your application. Refer to the appropriate section to review the instructions for your specific model.
group A DIP switches (All Models)
Using a small tool, configure your Inverter/Charger by setting the four Group A DIP Switches (located on the front panel of your unit; see
diagram) as follows:
Select Battery Type—REQUIRED
A1
CAUTION: The Battery Type DIP Switch setting must match
the type of batteries you connect, or your batteries may be
degraded or damaged over an extended period of time. See
"Battery Selection" section for more information.
Battery Type
Switch Position
AGM/Gel Cell (Sealed) Battery
Wet Cell (Vented) Battery
Select Low AC Input Voltage Point for
A4
A3
Switching to Battery—OPTIONAL*
Voltage and Level
120V Models
230V Models
Switch Position
A 105V
201V
A4 Up & A3 Up
B 95V
182V
A4 Up & A3 Down
C 85V
163V
A4 Down & A3 Up
D 75V
144V
A4 Down & A3 Down
(factory setting)
* Most of your connected appliances and equipment will perform adequately when your
Inverter/Charger's Low AC Voltage Input Point (DIP Switch #3 and #4 of Group A) are set
to Level B (95V for 120V Models/182V for 230V Models). However, if the unit frequently
switches to battery power due to momentary low line voltage swings that would have little
effect on equipment operation, you may wish to adjust this setting. By decreasing the Low
AC Voltage Input Point, you will reduce the number of times that your unit switches to
battery due to voltage swings.
B4
B3
B2
B1
Group B Dip Switches
A4
A3
A2
A1
Up
Down (factory setting)
A4
A3
A2
A1
A4
A3
A2
A1
A4
A3
A2
A1
A4
A3
A2
A1
INPUT C/B 10A
Select Charger Enable/Inhibit
A2
Switch is preset to ENABLE, which
permits continuous battery charging.
If you are connecting your unit to
batteries with a separate charger, you may
set this switch to INHIBIT to disable its
built-in charger to prevent overcharging.
Battery Type
Inhibit
Enable
Level A
Level B
Level C
Level D
5
A4
A3
A2
A1
OUTPUT C/B 12A
Group A Dip Switches
A4
A3
A2
Switch Position
Up
Down (factory setting)
A1
INHIBIT
ENABLE