P05 - Control logic
When P05 appears on the screen, the thermal regulation
system control logic is displayed.
(00 = 2 point control, 01 = proportional control, 02 =
fan coil control)
The thermal regulation system control logic cannot be
changed locally.
If the control is set to 2 points, go to point P09, if set to fan
coil, go to point P10, if proportional, go to point P06.
2 POINT CONTROL
The thermal regulation system is switched off when the
ambient temperature is equal to the set point, and is
switched back on when:
- the temperature is equal to or lower than the set point -
heat for heating;
- the temperature is equal to or higher than the set point +
cond for air-conditioning;
The diagrams below show the two function types.
set point
A
IR CONDITIONING
To avoid continuous switchings, the thermostat will wait for
up to 2 minutes before sending the activation command to
the actuator that controls the thermal regulation system.
heat
cond