Ex input
CH1 (terminal 41,42,43,44)
CH2 (terminal 51,52,53,54)
Vt (U
):
8.7 V
o
It (I
):
18.4 mA
o
P
:
40 mW
o
Lo/Ro
892 μH/Ω
IIC /
IIB /
Group A,B
Group C,E,F
C
/ C
5 μF
50 μF
a
o.
L
/ L
100 mH
300 mH
a
o.
U
:
10 V
i
I
:
30 mA
i
C
:
30 nF
i
820 nH
L
i.
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
Zone 2 installation:
Voltage max:
Power max:
Current max:
Installation notes:
The installation and wiring shall be in accordance with the National Electrical Code NFPA 70 ,
Article 500 or 505.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with
cable ends.
For installation on the 9400 Power Rail the power must be supplied from Power Control Module
Unit 9410.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer
enclosure having an IP protection of at least IP54.
The module is galvanic isolated and does not require grounding.
Install in pollution degree 2 or better.
Use 60 / 75 ºC Copper Conductors with wire Size AWG: (26-14).
Warning: Substitution of components may impair intrinsic safety.
Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing
and do not separate connectors when energized and an explosive gas mixture is present.
Warning: Do not mount or remove modules from the Power Rail when an explosive gas
mixture is present.
Revision date:
2009-08-24
9113 - Product Version 9113-001
IIA /
Group D,G
1000 μF
700 mH
125VAC / 110VDC
62,5VA / 32W
0.5A AC / 0.3ADC
32VAC / 32VDC
16VA / 32W
0.5A AC / 1ADC
Version Revision:
V2 R0
9113QF01
Prepared by:
PB
Page:
2/3