Ex input
CH1 (terminal 41,42,43,44)
CH2 (terminal 51,52,53,54)
U
:
8.7 V
o
I
:
18.4 mA
o
P
:
40 mW
o
Lo/Ro
892 μH/Ω
IIC
IIB
C
5 μF
50 μF
o.
L
100 mH
300 mH
o.
U
:
10 V
i
I
:
30 mA
i
C
:
30 nF
i
L
820 nH
i.
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
Zone 2 installation:
Voltage max:
Power max:
Current max:
Installation notes:
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection
of at least IP54 conforming to the requirements of EN60079-15.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
In type of protection "intrinsic safety iD" the parameters for intrinsic safety for gas group IIB are
applicable.
After the sensor circuits (Terminals 41..44, 51..54) have been installed in a type of protection, other
than "intrinsic safety" the module shall not be re-installed in type of protection "intrinsic safety"
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Revision date:
2009-08-24
9113 - Product Version 9113-001
IIA
1000 μF
700 mH
125VAC / 110VDC
62,5VA / 32W
0.5A AC / 0.3ADC
32VAC / 32VDC
16VA / 32W
0.5A AC / 1ADC
Version Revision:
V2 R0
9113QA01
Prepared by:
PB
Page:
2/3