Basic Operation
Error Messages
The UPS reports BATTERY REPLACEMENT and OVERLOAD STATUS using the
REPLACE BATTERY LCD SCREEN
In the event that the UPS battery requires replacement, the
light. Replace the UPS battery to reset the replace-battery indicator.
CRITICAL FAULT SCREENS
Some more severe fault conditions will result in the UPS shutting off power to the UPS-supported output receptacles. At this point, the LCD
screen will report any one of 5 possible on-screen fault codes. Some faults, such as output short circuit, overload and bad battery can be
user-corrected by removing the short, reducing the load or replacing the battery. Some fault conditions involving the battery charger and output
voltage may require repair or replacement in order to restore normal operation.
If a critical fault occurs, the LCD display will show the following error codes.
Note: The backlight will always illuminate whenever a fault or warning occurs.
Error Code Critical Fault
E01
OUTPUT SHORT
E02
OVER LOAD (LINE MODE OVERHAUL) Remove excess load, check load meter on LCD for load status.
E04
BATTERY MODE HIGH OUTPUT
E05
OVER CHARGE
E06
BATTERY LOW VOLTAGE
and the
OVERLOAD LCD SCREEN
icon will
If there is an overload, the
report the output load percentage.
Solution
Disconnect load(s) from UPS outlets. Power off UPS and contact Tripp Lite Technical
Support for assistance.
Turn off power to the UPS and contact Tripp Lite Technical Support for assistance.
Unplug UPS and contact Tripp Lite Technical Support for assistance.
Replace battery and contact Tripp Lite Technical Support if problem persists.
7
icons.
icon will light and the LCD screen will