Sperian Fendall Pure Flow 1000 Manual De Instalación Y Funcionamiento página 2

Ocultar thumbs Ver también para Fendall Pure Flow 1000:
Tabla de contenido
Do you need help installing your Fendall Pure Flow 1000
Please visit our website for the new Fendall Pure Flow 1000 Installation Video
Call Customer Service at 1-800-336-3255 for your FREE copy of the new
• The Fendall Pure Flow 1000 Emergency Eyewash Station is not for outside use. Do not install the Eyewash Station in an
outside location. Installation of the Eyewash Station in an outside location may prevent the unit from functioning properly in
an emergency situation.
• The unit must be level for proper operation. Failure to properly mount the unit may cause the unit to function improperly
at the time of an emergency.
• The Fendall Pure Flow 1000 may weigh approximately 100 pounds when installed with two cartridges. Assistance may be
required when installing the Eyewash Station and/or replacement cartridges.
• The area under the Fendall Pure Flow must be kept clear to allow reservoir to drop.
• Two Fendall Pure Flow cartridges must be used for unit to function properly.
• When installing the Fendall Pure Flow cartridges, the left-hand and right-hand nozzles must be touching in the middle. Failure
to install the nozzles so that they touch may result in the improper operation of the eyewash unit.
• Employees must be instructed in the use of Emergency Eyewash Stations.
• This Emergency Eyewash unit is intended for the emergency first aid of victims exposed to fluid chemical or soft particle
eye contamination until medical treatment is obtained. In all cases, the victim should seek medical attention
immediately after flushing.
• An individual or department must inspect this unit on a monthly basis. Records of these monthly inspections should be
kept with the unit.
• Never use an expired Sperian Saline cartridge. Use of an expired cartridge may result in serious personal injury or serious
illness, including blindness.
• During inspection, do not lift activating door as fluid flow will begin. Once fluid flow has started, it cannot be stopped.
Failure to follow and comply with all instructions and cautions stated in this manual may result in serious personal injury,
blindness, or death.
The ANSI Standard Z358.1-2009 requires that:
1. The unit shall be positioned with the fluid nozzle(s) not less than 83.8 cm (33 in.) and no greater than 114.3 cm (45 in.)
from the surface on which the user stands and 15.3 cm (6 in.) minimum from the wall or nearest obstruction.
2. Eyewash units shall be in accessible locations that require no more than 10 seconds to reach. The eyewash shall be
located on the same level as the hazard and the path of travel shall be free of obstructions that may inhibit the
immediate use of the equipment. For a strong acid or a strong caustic, the eyewash should be immediately adjacent to
the hazard.
3. Each eyewash location shall be identified with a highly visible sign positioned so the sign shall be visible within the area
served by the eyewash. The area around the eyewash shall be well lighted.
It is recommended that a consulting physician or appropriate professional be contacted for advice on the proper distance away
from hazard to install the eyewash unit.
2
at www.sperian.com
Fendall Pure Flow 1000 Installation Video
WARNING
OR
cartridges?
®
Tabla de contenido
loading

Este manual también es adecuado para:

32-001000

Tabla de contenido