LG MS15SQNB0 Manual De Instalación página 21

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 57
3
When needed to extend the drain hose of
indoor unit, assembly the drain pipe as
shown on the drawing
Drain pipe
Vinyl tape(narrow)
Adhesive
Wrap the insulation material
around the connecting portion.
1
Overlap the connection pipe insulation
material and the indoor unit pipe insulation
material. Bind them together with vinyl
tape so that there may be no gap.
2
Set the tubing cutting line upward.
Wrap the area which accommodates the
rear piping housing section with vinyl tape.
Cutting Line
Gas Pipe
Liquid Pipe
Good Case
* Tubing cutting line have to be upward.
Connection pipe
Vinyl tape (wide)
Wrap with vinyl tape
Connecting cable
Vinyl tape(narrow)
Indoor unit drain hose
Insulation material
Cutting Line
Bad Case
Indoor unit pipe
Pipe
THE INDOOR UNIT INSTALLATION
3
Bundle the piping and drain hose together
by wrapping them with vinyl tape sufficient
enough to cover where they fit into the
rear piping housing section.
Wrap with vinyl tape
Pipe
Drain hose
CAUTION
!
• When mechanical connectors are
reused indoors, sealing parts shall be
renewed.
• When flared joints are reused indoors,
the flare part shall be re-fabricated.
21
Vinyl tape(wide)
Tabla de contenido
loading

Tabla de contenido