9.8.6 Number of ClO
batches
2
1. "main menu > service > process > production ClO2".
After 9999 batches, the display is reset to 0.
production ClO2
25
batches

9.8.7 Maintenance date

1. "main menu > service > process > production ClO2 >
maintenance".
maintenance
LAST
2012-07-25
NEXT
2013-07-25
9.8.8 Resetting the chemical consumption after changing
containers
The controller calculates the chemical consumption and displays
it in liters. It starts automatically at 0.000 liters.
Displaying the chemical consumption
1. "Main menu > Service > Process > Production ClO2 >
Chemicals"
chemicals
HCl
NaClO2
reset
2. HCl > [OK].
HCl
0.000 L
since 2012-04-29
3. Use the same procedure to see consumption of both NaClO2
and HCl.
Resetting the chemical consumption
1. "Production ClO2 > Chemicals > reset"
reset
HCl
NaClO2
2. HCl > [OK]. The counter is reset to 0.
3. NaClO2 > [OK]. The counter is reset to 0.
9.8.9 Indicating the "age of ClO2" in the reaction tank and in
batch tank
1. "Main menu > Service > Process > Production ClO2".
production ClO2
batches
chemicals
maintenance
age of ClO2
2. The "Age" of ClO2 is shown in hh:mm:s.
age of ClO2
reaction tank
03:16
int. batch tank
00:00
3. Press [Esc].

9.8.10 Testing the display

1. "main menu > service >
2. "Test display" > [OK].
The test function is started. The display goes completely dark, so
that each pixel can be checked. In addition, all LEDs are switched
on. They light up orange, and the red alarm LED flashes.
After about 8 seconds, the display returns to the "service > test
display" submenu.
39