BTL7-A/C/E/G5 _ _ -M _ _ _ _ -K(8)-SR32/SR115/_ _ _
Micropulse Transducer - Rod Style
8
Adjusting (continued)
Set end point
► Bring magnet to the new end point.
► Activate
b
for at least 2 s.
⇒ The new end point is set with the last valid end
value.
Adjust end value
► The end value can be changed using
gradient of the curve changes (see page 15).
► End calibration procedure: Briefly press
simultaneously (< 1 s).
⇒ Set position value is saved.
End adjustment
► Briefly activate
a
and
⇒ The current position value is displayed once the
buttons are released.
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
18
english
and
. The
a
b
a
and
b
simultaneously (< 1 s).
b
b
> 2 s
a
a
b
b
a
b
< 1 s
a
b
< 1 s
Displayed values (example)
At 0...10 V
At 4...20 mA
9.89 V
19.13 mA
10.00 V
20.00 mA
10.00 V
20.00 mA
8.00 V
16.80 mA
2.00 V
6.00 mA
8.00 V
16.80 mA
10.50 V
3.60 mA
7.63 V
18.56 mA